(!) Since support from Microsoft will end on January 14th, 2020, Windows 7 will be excluded from the recommended environment from December 15th, 2019 on this site. Vì lý do Microsoft kết thúc hỗ trợ cho Windows 7 vào ngày 14/01/2020, Windows 7 sẽ là hệ điều hành không được khuyến khích sử dụng với trang web này từ ngày 15/12/2019.
Select part number to Order Now/ Add to Cart
Part Number | NF63-CVF | ||||||||
---|---|---|---|---|---|---|---|---|---|
Rated current In Standard ambient temperature 40°C A | (3)(5) 10 15 20 30 40 50 | 60 | (63) | ||||||
Number of Positions | 2 | 3 | 2 | 3 | 2 | 3 | |||
Rated insulation voltage Ui V | 440 | 440 | 440 | ||||||
Rating Short circuit Break Capacity kA | JIS C 8201-2-1 Ann.1 JIS C 8201-2-1 Ann.2 IEC 60947-2 EN 60947-2 (lcu/lcs) | AC | 690 V | - | - | - | |||
500 V | - | - | - | ||||||
440 V | 2.5/2.5 | 2.5/2.5 | 2.5/2.5 | ||||||
415 V | 5/5 | 5/5 | 5/5 | ||||||
400 V | 5/5 | 5/5 | 5/5 | ||||||
380 V | 5/5 | 5/5 | 5/5 | ||||||
230 V | 7.5/7.5 | 7.5/7.5 | 7.5/7.5 | ||||||
DC (*1) | 250 V | - | - | - | |||||
125 V | - | - | - | ||||||
GB 14048.2 (lcu/lcs) | AC | 415 V | 5/5 | 5/5 | 5/5 | ||||
400 V | 5/5 | 5/5 | 5/5 | ||||||
380 V | 5/5 | 5/5 | 5/5 | ||||||
230 V | 7.5/7.5 | 7.5/7.5 | 7.5/7.5 | ||||||
DC (*1) | 250 V | - | - | - | |||||
125 V | - | - | - | ||||||
Parts included as standard (Surface type) | IEC 35 mm rail mounting clip Insulation barrier (2-position 2 sheets, 3-position 4 sheets) |
*(1) For 3-position products, use 2 positions.
Note (1) The mounting screws must be prepared by the customer. (Recommended size: M4 × 0.7 × 65 [2 pcs.])
Part Number | NF125-CVF | ||||||
---|---|---|---|---|---|---|---|
Rated current In Standard ambient temperature 40°C A | 60 75 100 | 125 | |||||
Number of Positions | 2 | 3 | 2 | 3 | |||
Rated insulation voltage Ui V | 600 | 600 | |||||
Rating Short circuit Break Capacity kA | JIS C 8201-2-1 Ann.1 JIS C 8201-2-1 Ann.2 IEC 60947-2 EN 60947-2 (lcu/lcs) | AC | 690 V | - | - | ||
500 V | 7.5/4 | 7.5/4 | |||||
440 V | 10/5 | 10/5 | |||||
415 V | 10/5 | 10/5 | |||||
400 V | 10/5 | 10/5 | |||||
380 V | 10/5 | 10/5 | |||||
230 V | 30/15 | 30/15 | |||||
DC (*1) | 250 V | 7.5/4 | 7.5/4 | ||||
125 V | 7.5/4 | 7.5/4 | |||||
GB 14048.2 (lcu/lcs) | AC | 415 V | 10/5 | 10/5 | |||
400 V | 10/5 | 10/5 | |||||
380 V | 10/5 | 10/5 | |||||
230 V | 30/15 | 30/15 | |||||
DC (*1) | 250 V | 7.5/4 | 7.5/4 | ||||
125 V | - | - | |||||
Parts included as standard (Surface type) | IEC 35-mm rail mounting clip Insulation barrier (2-position 1 pc., 3-position 2 pcs.) Mounting screw M4 × 0.7 × 55 (2 pcs.) |
*(1) For 3-position products, use 2 positions.
NF63-CVF
Surface type
Note (1) Cables cannot be directly connected.
(2) The motor breaker has only 3 positions.
NF125-CVF
Surface type
Part Number |
---|
NF63-CVF 2P 5A |
NF63-CVF 2P 63A |
NF63-CVF 3P 5A |
Part Number | Price | Minimum Order Qty. | Volume Discount | Days to ShipSố ngày giao hàng | Ampere frame | Rated block capacity AC 200 V (kA) | Rated Braking Capacity at Rated Voltage of VDC 250 (kA) | Rated block capacity, voltages except VAC 100/200/400, VDC 250 | Number of Poles | Rated Current (A) | Mounting Method | Connection Method | Representative Standard | Dimension height (mm) | Dimension width (mm) | Dimension depth (mm) | Type | Rated block capacity AC 415 V (kA) | Rated block capacity AC 230 V (kA) |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
881,250 VND | 1 Piece(s) | Quote | 63AF | 7.5 | - | Available | 2 | 5 | DIN rail mount | Surface type | PSE / CE / CCC | 100 | 36 | 90 | No fuse breaker | 5 | 7.5 | ||
1,327,500 VND | 1 Piece(s) | Quote | 63AF | 7.5 | - | Available | 2 | 63 | DIN rail mount | Surface type | PSE / CE / CCC | 100 | 36 | 90 | No fuse breaker | 5 | 7.5 | ||
1,113,750 VND | 1 Piece(s) | Quote | 63AF | 7.5 | - | Available | 3 | 5 | DIN rail mount | Surface type | PSE / CE / CCC | 100 | 54 | 90 | No fuse breaker | 5 | 7.5 |
Loading...Tải…
Rated block capacity AC 400 V(kA) | 5 |
---|
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy